Firefighter Shut-Off Specs

The Little Firefighter Automatic Shut-Off Valve is the most lightweight and compact valve sold on the market. Automatically shuts off gas when triggered by a significant seismic event. Easy 1/8 turn of coin slot for emergency manual shut-off. Complies with all codes. It comes with a 30 year warranty on all parts.

Order This Valve! | Warranty

Please take a moment to understand the simplicity of our valves operation. It has been our experience the the simpler the operation the more consist ant and accurate the function when needed. Each valve is tested and certified before leaving our factory insuring it meets UL and Los Angeles Counties strict approvals.

  • Both Valve Styles Shut-Off Gas Flow When Triggered by a 5.4 Magnitude Earthquake at the Valves Location.
  • All Designs are Patented or Patent Pending
  • Valves Have Been Tested to ASCE 25-97, State of California 12-23-1 & ANSI Z21.70-1981 Standards for Seismic Gas Valves

"Designed to shut-off gas flow to your home in an earthquake and reduce destructive fires."

Firefighter Gas Safety 3/4" Valves

Dependable and safe your family is protected from earth quake related gas fires 24-7 whether your home or not our AGV-75 & VAGV-75 gas valves bring you piece of mind. Our gas valves meet or exceed the requirements of the City of Los Angeles, along with UL Laboratory certification. When safety counts, depend on Fire Fighter Gas Safety Products.

  • Complies With All State, City, & Laboratory Testing Requirements
  • Most Compact State-of-the-Art Design
  • Best Flow On The Market
  • Limited warranty (see Installation Instructions page for details)
  • Automatically Shuts-Off Gas When Triggered by a 5.4 Magnitude Seismic Event
  • Manual Reset Available On Both Sides
  • Endorsed By the Los Angeles Area PHCC
3/4" Gas Shut-Off Valve Specifications
Model#
Pipe Size
Max.
Pressure
Length
Width
Height
Weight

0.5"W.C
BTU/HR
x1000

1.0"W.C
BTU/HR
x1000
Effective
Pipe
Length
Cv
Value
AGV-75 Horizontal
3/4" npt
5 psi 3"
1-1/2"
3"
1 lbs.
692
977
3.4'
18.1
VAGV-75 Vertical
3/4" npt
10 psi 2-1/2"
2"
3-3/8"
1 lbs.
600
895
3.0
16.4

Firefighter Gas Safety 1" Valves

The AGV-100, HAGV-100 & HAGV-100-HP series valves are use in large homes and some small industrial applications. At your home or office our valves work 24-7 to protect lives and property from earth quake related gas fires. Please remember our gas valves meet or exceed the requirements of the City of Los Angeles, and are UL Laboratory tested and certified. When safety counts, depend on Fire Fighter Gas Safety Products.

  • Complies With All State, City, & Laboratory Testing Requirements
  • Most Compact State-of-the-Art Design
  • Best Flow On The Market
  • Limited warranty (see Installation Instructions page for details)
  • Automatically Shuts-Off Gas When Triggered by a 5.4 Magnitude Seismic Event
  • Manual Reset Available On Both Sides
  • Endorsed By the Los Angeles Area PHCC
1" Gas Shut-Off Valve Specifications
Model#
Pipe Size
Max.
Pressure
Length
Width
Height
Weight

0.5"W.C
BTU/HR
x1000

1.0"W.C
BTU/HR
x1000
Effective
Pipe
Length
Cv
Value
AGV- 100 Horizontal
1" NPT
5 psi 4"
1-3/4"
3-1/2"
1.5 Lbs.
1,153
1,628
4.5'
30.2
VAGV- 100 Vertical
1" NPT
10 psi 2-1/2"
2"
3-3/8"
1 Lbs.
515
765
10.0'
14.1

Firefighter Gas Safety 1 1/4" Valves

The AGV-125, HAGV-125 & HAGV-125-HP series valves are use in large homes and some small industrial applications. At your home or office our valves work 24-7 to protect lives and property from earth quake related gas fires. Please remember our gas valves meet or exceed the requirements of the City of Los Angeles, and are UL Laboratory tested and certified. When safety counts, depend on Fire Fighter Gas Safety Products.

  • Complies With All State, City, & Laboratory Testing Requirements
  • Most Compact State-of-the-Art Design
  • Best Flow On The Market
  • Limited warranty (see Installation Instructions page for details)
  • Automatically Shuts-Off Gas When Triggered by a 5.4 Magnitude Seismic Event
  • Manual Reset Available On Both Sides
  • Endorsed By the Los Angeles Area PHCC
1-1/4" Gas Shut-Off Valve Specifications
Model#
Pipe Size
Max.
Pres.
Length
Width
Height
Weight

0.5"W.C
BTU/HR
x1000

1.0"W.C
BTU/HR
x1000
Effective
Pipe
Length
Cv
Value
AGV-125 Horizontal
1-1/4"npt
5 psi 4"
2-1/3"
4-2/3"
3 lbs.
1,889
2,677
6.9'
49.6
VAGV-125 Vertical
1-1/4"npt 10 psi 2.5" 2" 3.4" 1 lbs. 440 650 75.0' 12.0
VAGV-125-HF Vertical
1-1/4"npt 2 psi 4.2" 3.3" 5.2" 7 lbs. 2,400 3,700 4.0' 56.5

Firefighter Gas Safety 1 1/2" Valves

The AGV-150, AGV-150-HP, HAGV-150& HAGV-150-HP series valves are use in commercial applications. At your office our valves work 24-7 to protect lives and property from earth quake related gas fires. Please remember our gas valves meet or exceed the requirements of the City of Los Angeles, and are UL Laboratory tested and certified. When safety counts, depend on Fire Fighter Gas Safety Products.

  • Complies With All State, City, & Laboratory Testing Requirements
  • Most Compact State-of-the-Art Design
  • Best Flow On The Market
  • Limited warranty (see Installation Instructions page for details)
  • Automatically Shuts-Off Gas When Triggered by a 5.4 Magnitude Seismic Event
  • Manual Reset Available On Both Sides
  • Endorsed By the Los Angeles Area PHCC
1-1/2" Gas Shut-Off Valve Specifications
Model#
Pipe Size
Max.
Pressure
Length
Width
Height
Weight

0.5"W.C
BTU/HR
x1000

1.0"W.C
BTU/HR
x1000
Effective
Pipe
Length
Cv
Value
AGV- 150 Horizontal
1-1/2"npt
5 psi 6"
3"
5-1/2"
6 lbs.
4,079
5,759
10.0"
107.0
VAGV- 150 Vertical
1-1/2"npt 2 psi 4.2" 3.3"" 5.2" 7 lbs. 2,400 3,700 6.0' 68.8
AGV-150-HP Horizontal
1-1/2"npt 60 psi 6" 3" 5-1/2" 6 lbs. 4.079 5,759 10.0' 107.0
VAGV-150-HP Vertical
1-1/2"npt
60 psi 4.2"
3.3"
5.2"
7 lbs.
2,400
3,700
6.0'
68.8

Firefighter Gas Safety 2" Valves

The AGV-200, AGV-200-HP, HAGV-200 & HAGV-200-HP series valves are use in commercial and large business applications. At your office our valves work 24-7 to protect lives and property from earth quake related gas fires. Please remember our gas valves meet or exceed the requirements of the City of Los Angeles, and are UL Laboratory tested and certified. When safety counts, depend on Fire Fighter Gas Safety Products.

  • Complies With All State, City, & Laboratory Testing Requirements
  • Most Compact State-of-the-Art Design
  • Best Flow On The Market
  • Limited warranty (see Installation Instructions page for details)
  • Automatically Shuts-Off Gas When Triggered by a 5.4 Magnitude Seismic Event
  • Manual Reset Available On Both Sides
  • Endorsed By the Los Angeles Area PHCC
2" Gas Shut-Off Valve Specifications
Model#
Pipe Size
Max.
Pressure
Length
Width
Height
Weight

0.5"W.C
BTU/HR
x1000

1.0"W.C
BTU/HR
x1000
Effective
Pipe
Length
Cv
Value
AGV-200 Horizontal
2" npt
5 psi 6"
3"
5-1/2"
6 lbs.
4,079
5,759
10.0'
107.0
VAGV-200 Vertical
2" npt 2 psi 4.2" 3.3" 5.2" 7 lbs. 1,800 2,500 40.0' 46.8
AGV-200-HP Horizontal
2" npt 60 psi 6"
3"
5-1/2"
6 lbs.
4,079
5,759
10.0'
107.0
VAGV-200-HP Vertical
2" npt
60 psi 4.2"
3.3"
5.2"
7 lbs.
1,800
2,500
40.0'
46.8

Firefighter Gas Safety Industrial Valves

These industrial sized AGV-series valves are milled from solid aluminum and are specifically made for industry. Our gas valves meet or exceed the requirements of the City of Los Angeles, and are laboratory tested and certified. When safety counts, depend on Firefighter Gas Safety Products.

  • Complies With All State, City, & Laboratory Testing Requirements
  • Most Compact State-of-the-Art Design
  • Best Flow On The Market
  • Limited warranty (see Installation Instructions page for details)
  • Automatically Shuts-Off Gas When Triggered by a 5.4 Magnitude Seismic Event
  • Manual Reset Available On Both Sides
  • Endorsed By the Los Angeles Area PHCC
Industrial Sized Gas Shut-Off Valve Specifications
Model#
Pipe Size
Max.
Pressure
Length
Width
Height
Weight
Effective
Pipe
Length
Cv
Value
AGV-250 Horizontal
2.5" npt
60 psi 6.8"
3.6"
6.2"
9 lbs.
4'
252
AGV-250 Horizontal
3" npt 60 psi 8.4" 4.5" 8.2" 14 lbs. 5' 410.6
AGV-400 Horizontal
4" npt 60 psi 10.1"
5.9"
9"
22 lbs.
12.0'
536.8

Flow Capacity Tables (SCFH) - AGV-250

Pressure Drop Inlet Pressure (psi)
psi iwc 3 7 10
0.018 .5 4311 6597 7888
.036 1 6079 9317 11145
.072 2 8544 13143 15733
.108 3 10400 16054 19234
.144 4 11934 18490 22169
.18 5 13258 20618 24740

Flow Capacity Tables (SCFH) - AGV-300

Pressure Drop Inlet Pressure (psi)
psi iwc 3 7 10
0.018 .5 7025 10749 12852
.036 1 9904 15181 18159
.072 2 13921 21414 25635
.108 3 16945 26159 31339
.144 4 19444 30126 36121
.18 5 21602 33594 40311

Flow Capacity Tables (SCFH) - AGV-400

Pressure Drop Inlet Pressure (psi)
psi iwc 3 7 10
0.018 .5 9184 14052 16802
.036 1 12948 19847 23741
.072 2 18200 27996 33514
.108 3 22153 34199 40971
.144 4 25420 39386 47223
.18 5 28241 43919 52701